EVA processing temperature fluctuates

Sorun Belirtisi
During EVA processing, temperature fluctuates ±5-8°C, exceeding the ±2°C control accuracy
Neden Analizi
Improper PID parameters of the temperature control system; aging heater bands with uneven power; improper thermocouple position with measurement deviation
Çözüm
1) Re-calibrate PID parameters; 2) Replace aging heater bands; 3) Adjust thermocouple position to the center of the melt pool
Temel Çıkarım
Temperature fluctuation is caused by an improper temperature control system; PID calibration and heater band replacement are key
EVA temperature fluctuation PID calibration heater band thermocouple